Function Test Status L.E.D.
Normal 5 seconds discharge --
Monthly 30 minutes discharge Red
Half Year 60 minutes discharge
Fail to Test Flashing

Automatic Test : Real time clock - setting with 8 bit MCU
Function Test Exercise Status - Selectable
1 Week 30, 60, 90 and 120/180 minutes
2, 4, 6, 8 Weeks
12 Week
24 Week
Specification
Mode of Operation : Non - Maintained
Lamp : Tungsten Halogen or Dichroic Halogen, with 180º adjustable sets and plastic-cover anti-dust
Main Supply : AC 220 Volt, 50Hz, 10% Single Phase
Control System : 8 bit Micro Controller Unit (MCU) with solid state automatic battery charger full function low / high charge and discharge,low / high voltagecut - off preventing battery defects
Construction : Electro-Galvanized steel sheet 1 mm. with epoxy powder and stove enamel coated anti-rust corrosion proof or ABS Flame Retardant UL 94 V - O
Battery : Sealed lead acid battery, based on ISO 9001, ISO 14001 certified and UL
Charging Period : 15-20 Hours as required
Manual Test : Push Button and Infrared Remote Control as below features
Safety Features : ♦ Low - High voltage cut-off, preventing battery over discharge and recharge
♦ AC fuse - preventing short circuit and overload for main incoming AC 220 Volt
♦ DC fuse - preventing short circuit and overload for charging & load
Accessories : ♦ On / Off switch for lamps
♦ LED. AC indicates main incoming AC 220 Volt
♦ LED. FULL indicates charging, and fully charged
♦ LED. FAIL indicates fail to charge
♦ LED. AUTO - TEST indicates fully automatic functional
♦ LED. IR indicates infrared remote test functional
♦ Time Delay 1 up to 10 minutes
CP-M Series
Dichroic Halogen (square)

MODEL BATTERY BULBS
(Watt)
DURATION
(Hrs. Mins) _+10%
WEIGHT
(Kgs)
DIMENSION
W x L x H (cm)
CP 15-M 12V. 15Ah. 2 x 35
2 x 50
2.00
1.15
8.5 37 x 9 x 33.5
CP 18-M 12V. 18Ah. 2 x 35
2 x 50
2.30
1.40
9.2
CP 21-M 12V. 21Ah. 2 x 35
2 x 50
2.50
2.00
9.9
CP 23-M 12V. 24Ah. 2 x 35
2 x 50
3.00
2.10
10.6
CP 26-M 12V. 26Ah. 2 x 35
2 x 50
3.30
2.30
12.6
CP 35-M 12V. 35Ah. 2 x 35
2 x 50
4.45
3.15
15.0 37 x 16.5 x 33.5
CP 40-M 12V. 40Ah. 2 x 35
2 x 50
5.30
3.50
18.5

CP-M Series
Tungsten Halogen Lamp(rectangle)

MODEL BATTERY BULBS
(Watt)
DURATION
(Hrs. Mins) _+10%
WEIGHT
(Kgs)
DIMENSION
W x L x H (cm)
CP 15-M 12V. 15Ah. 2 x 35
2 x 50
2.00
1.15
8.5 37 x 9 x 33.5
CP 18-M 12V. 18Ah. 2 x 35
2 x 50
2.30
1.40
9.2
CP 21-M 12V. 21Ah. 2 x 35
2 x 50
2.50
2.00
9.9
CP 23-M 12V. 24Ah. 2 x 35
2 x 50
3.00
2.10
10.6
CP 26-M 12V. 26Ah. 2 x 35
2 x 50
3.30
2.30
12.6
CP 35-M 12V. 35Ah. 2 x 35 2 x 50 4.45 3.15 15.0 37 x 16.5 x 33.5
CP 40-M 12V. 40Ah. 2 x 35
2 x 50
5.30
3.50
18.5
emergency light cp - m series

Emergency lighting indicators

1. AC : Main incoming AC 220 Volt
2. FULL : Charge, and fully charged
3. FAIL : Fail to charge
4. AUTO TEST : Fully automatic functional
5. IR : Infrared remote test functional
6. BACK TIME (Minutes) : Record latest duration time
7. IR RECEIVER : Infrared receiver signal port
8. 60 minutes Test : Half year push button status
9. 30 minutes Test : Monthly push button status
10. Fail(TEST SYSTEM) : Fail to test half year and monthly status
11. Normal Test : Test battery 5 seconds discharge
12. Monthly Test : Test battery 30 minutes discharge
13. Half Year Test : Test battery 60 minutes discharge
14. On / Off switch : Switch on / off for lamps
15. AC FUSE : Preventing short circuit and overload for main incoming AC 220 Volt